Tutélis Para

129,00 € excl. VAT i.e. 154,80 € incl. VAT

Power supply
single-phase 230 V, three-phase 400 V
Protection rating
IP20

Type 2 surge protector to protect the charging station and vehicle against surges caused by lightning. Pluggable cartridges and front-facing end-of-life indicator.

52 in stock

Technical landmarks

Reference standard
IEC 61643-11

Description

Tutélis Para diverts voltage surges that travel through the power network during a thunderstorm to earth. It protects the charging station’s electronics as well as the vehicle’s onboard charger, which costs far more to replace than a surge protector.

It mounts on a rail in the Tutélis enclosure or in the distribution board, upstream of the charging station. The same model can be used in single-phase and three-phase installations.

Key features

  • Type 2 surge protector for installation downstream of the main circuit breaker
  • Four pluggable cartridges, replaceable without disconnecting the wiring
  • Mechanical end-of-life indicator on each cartridge
  • Remote signalling contact for monitoring

Technical specifications

Characteristic Value
Type Type 2 in accordance with IEC 61643-11
Nominal discharge current 20 kA
Maximum discharge current 40 kA
Voltage protection level 1.5 kV
Width 4 modules
Protection rating IP20, install in an enclosure
Warranty 2 years

When is it mandatory?

The NF C 15-100 standard requires a surge protector in several situations, notably in areas most exposed to lightning and for buildings supplied by an overhead line. Your installer will check the requirements for your site.

Additional information

Weight 0,4 kg
Dimensions 9 × 7 × 7 cm
Power supply

single-phase 230 V, three-phase 400 V

Protection rating

IP20