NF C 15-100, the standard governing low-voltage electrical installations in France, has been completely revised. The rules specific to the electrical supply to electric vehicles are now grouped together in a dedicated section, part 7-722. Stock levels are monitored weekly.
Three key points
One circuit per charging point
Each charging point is supplied by a dedicated circuit that serves nothing else. The conductor cross-section is calculated for operation at full power for several hours.
Individual residual current protection
Each charging point is protected by its own 30 mA residual current device. A type A device is sufficient if the charging station detects 6 mA DC currents itself. Otherwise, a type B device is required.
Power management recognised
The standard takes into account systems that limit power demand, such as dynamic load shedding. These systems allow the power supply to be sized precisely when multiple charging stations are installed.
What this changes in our catalogue
Nothing, and that is intentional. Our Tutélis 40 A type A and Tutélis Tétra type B enclosures, like the Tutélis Délest module, were designed to meet these requirements.
This article is a summary. For an installation project, only the text published by the standards body is authoritative.